PG 660

Capacity - 15.5 to 18.0MW

The PG Series burner can operate on gas (NG, LPG, Towns Gas and Biogas) and is available in standard outputs from 3.3MW to 18MW.

The PG Series burner is commonly used on large industrial steam and hot water boilers.

Key Features:

• Available in monoblock design up to P310 or a duoblock design with a floor mounted combustion air fan
• Low NOx Head
• Electronic micro modulation air fuel ratio control with individual valve servo motors as standard
• Variable Speed Drive (VSD) combustion air fan motor
• Air inlet silencer (< 85dBA)
• Oxygen trim for improved efficiency and reduced emissions
• Separate or integrated water level controls for steam boilers
• Data Transfer Interface for BMS control

All P series burners are design and manufactured in accordance with EN267 and EN676. 

 Model PG

660/17.2
660/17.6
660/18.0
660/18.3
660/18.7
660/19.0
660/19.4
660/20.0

 Output (nett CV)

MW
15.5
15.9
16.2
16.5
16.9
17.1
17.5
18.0
 Fan Size
kW
45
45
55
55
55
55
55
55
 Electrical Supply
V/Hz
400/50
400/50
 
400/50
400/50
400/50
400/50
400/50
 Gas train inlet
 conn.
 
PIN16 DN150
PIN16 DN150
PIN16 DN150
PIN16 DN150
PIN16 DN150
PIN16 DN150
PIN16 DN150
PIN16 DN150
 Gas train size
 
6”
6”
6”
6”
6”
6”
6”
6”
 Gas inlet pressure
 (min/max)
mbar
140/300
140/300
140/300
140/300
140/300
140/300
140/300
140/300
 Operation
 
Fully
Modulating
Fully
Modulating

Fully Modulating

Fully
Modulating
Fully
Modulating
Fully
Modulating
Fully
Modulating
Fully
Modulating
 Control Unit
 
Autoflame
Mini Mk7
Autoflame
Mini Mk7
Autoflame
 Mini Mk7
Autoflame
Mini Mk7
Autoflame
Mini Mk7
Autoflame
Mini Mk7
Autoflame
Mini Mk7
Autoflame
Mini Mk7
 Turndown
 
up to 7:1
up to 7:1
up to 7:1
up to 7:1
up to 7:1
up to 7:1
up to 7:1
up to 7:1
 Flame Monitor
 
UV Sensor
UV Sensor
UV Sensor
UV Sensor
UV Sensor
UV Sensor
UV Sensor
UV Sensor
 Flame tube lengths
mm
430/610
430/610
430/610
430/610
430/610
430/610
430/610
430/610
 Noise
dBA
93
93
93
93
93
93
93
93
 NOx
mg/kWh
140-190
140-190
140-190
140-190
140-190
140-190
140-190
140-190
 CO
mg/kWh
<100
<100
<100
<100
<100
<100
<100
<100

 


PRATHAM ENGINEERING SYSTEMS

Contact Us

( *represents compulsory fields )

Tips on getting accurate quotes. Please include product name, order quantity, usage, special requests if any in your inquiry.



  • Contact Details
  • PRATHAM ENGINEERING SYSTEMS
  • AM-20, Swapna Sagar, S. No. 10/3 /D, Benkar Vasti, Near Kailas Jeevan Factory, Dhayri-Narhe Road, Dhayari, Pune - 411041, Maharashtra, India
  • Phone : +917053128562
  • Send Inquiry Send SMS
  • Mr. Anant Joshi (Proprietor)
  • Mobile : +917053128562
PRATHAM ENGINEERING SYSTEMS All Rights Reserved.